Post Offer Free
Gold Co.,Ltd
Gold Co.,Ltd  

Gold Index: 18382

You are here: home  > Electrical  > CT and PT Analyzer

CT and PT Analyzer 

Price: 2.0 USD 
Payment Terms: T/T,L/C,D/A,D/P,WU,Paypal,Money Gram 
Place of Origin: Chongqing, China (Mainland) 
inquire
Add to My Favorites
HiSupplier Escrow
Share |

Product Detail

Model No.: GDVA-405
Production Capacity: 500Sets/per Month
Delivery Date: 10days
PT Analyzer: CT Analyzer
Means of Transport: Ocean,Land,Air
Packing: Wooden Case
Tester: Transformer Tester
Current Transform Analyzer: Power Analyzer

GDVA-405 CT PT Analyzer

GDVA-405 CT PT Analyzer

Introduction:

Tests for Current Transformer:

l  Excitation curve and parameters test

l  Turns ratio test

l  Ratio and phase error test

l  Polarity mark check

l  Winding resistance measurement

l  Secondary loop burden measurement

l  Error line curve test for protection CT

l  Transient CT parameters test

l  CT nameplate guess

l  Saturation hysteresis loop curve measurement

l Tests for Potencial Transformer:

l  Turns ratio test

l  Ratio error and phase angle error test

l  Polarity test

l  Secondary burden test

l  Winding resistance test

Applications of CT/ PT Analyzer:

l  CT nameplate check

l  CT parameters check in work burden

l  CT transient parameters analysis

l  CT ratio and phase error calibration

l  PT routine test

Specifications:

Test standards

IEC60044-1, IEC60044-6, IEC60044-2, IEC60044-5, C57.13

Power supply

 AC220V±10%, 50/60Hz±10%

Voltage output

 0.1~180V (AC)

Current output

 0.001~5A(RMS)

Power output

 500VA

Max.  knee voltage measurement

 45KV

Current measurement

 

 

  Range

0~10A (automatically change  range in 0.1/0.4/2/10A)

  Error

 <±0.1%+0.01%FS

 

Voltage measurement

 

 Range

0~200V (automatically change range in 1V/10V/70V/200V)

 Error

< ±0.1%+0.01%FS

Turns ratio measurement Range

  

1~35000

1~2000, error<0.05%

2000~5000,error<0.1%

5000~35000,error<0.2%

Phase measurement  

error

 ±2min

resolution

 0.01min

Winding resistance measurement

    

   

Range

0~8kΩ (automatically change range in2ohm/20ohm/80ohm/800ohm/8kohm)

Error

 < 0.2%RDG+0.02%FS

Maximum resolution :  0.1mΩ

Temperature measurement

-50~100 Celsius degree; error<3 Celsius degree

CT Secondary burden

Range

0~160ohm (automatically change range in 2ohm/20ohm/80ohm/160ohm)

Error

 <0.2%RDG+0.02%FS

Maximum resolution : 0.001ohm

   

  

PT Secondary burden

 

Error

0~80kohm (automatically change range in 800ohm/8kohm/80kohm)

Maximum

<0.2%RDG+0.02%FS

resolution

 0.1ohm

   

PT ratio measurement

 

Range

1~35000

1~10000 error<0.1%

10000~35000 error<0.2%

PT ratio error measurement :Typical error <0.05%,

Maximum Error<0.1%

PT phase angle measurement maximum error < 3min

Make evaluation for test results according to selected standards

Make word report for test result

Make word reports one time for multi-group test records on the PC

Calculate the ratio errors and phase angle errors at rated burden and working burden in one time test

Compare excitation curves with saved excitation curves in the same window

Memory capacity

 >1000 groups test results

Working condition temperature

 -10℃~50℃; moist ≤90%


bigPhoto
 Ms. cathy Jiang

Tel: 86-023-62984891
Contact to this supplier

Related Search

Find more related products in following catalogs on Hisupplier.com

Related Products

Company Info

Gold Co.,Ltd [China (Mainland)]


Business Type:Manufacturer, Trading Company
City: Chongqing
Province/State: Chongqing
Country/Region: China (Mainland)

You May Like: